This software applies to the following DEIF products:

You’re about to download 6.06.0

The main changes implemented since the last version are as follows:

PMS compatibility: 1.25.0

New features:
1- Scania EMS2 S8 Urea/DEF level added to delta alarms.
2- PMS function: block breaker in closed position when one or two faults occur added (menu 8860 and 8870).

Finetuning:
1- TDU can now show the DEF level when Scania EMS2 S8 is used as engine I/F.
2- 32-bit EIC values is shown on new modbus (function 4, reg 26000).
3- IOM works with all supported engine protocols.
4- AMF Overlap is working when modeshift is used.

Ver. Date Description

6.06.0

18.02.2022

PMS compatibility: 1.25.0

New features:
1- Scania EMS2 S8 Urea/DEF level added to delta alarms.
2- PMS function: block breaker in closed position when one or two faults occur added (menu 8860 and 8870).

Finetuning:
1- TDU can now show the DEF level when Scania EMS2 S8 is used as engine I/F.
2- 32-bit EIC values is shown on new modbus (function 4, reg 26000).
3- IOM works with all supported engine protocols.
4- AMF Overlap is working when modeshift is used.

6.05.0

01.02.2022

PM compatibility: 1.24.2

New features:

  • Added supported ECU types.
  • NTP Support added.
  • Option A20: An external clearing time setting has been introduced in "Advanced Protection" under "Trip parameters".
  • Option A20: Sunspec model 707 and 708 now supported.
  • Option A20: Sunspec model 709 and 710 now supported.
  • Option A20: Sunspec model 703 now supported.
  • Option A20: Sunspec model 704 now supported.
  • Option A20: Sunspec model 705 now supported.
  • Option A20: Sunspec model 711 now supported.
  • Option A20: Q(U) VRef available in the DU-2, TDU and USW data tracer and trending.
  • Option A20: Sunspec model 702 now supported.
  • Option A20: Ability to disable option A20 functionality using menu 9101.
  • Option A20: Sunspec model 701 supported.
  • Option A20: Voltage ride through detection, regulation and protection (based on evaluation of cumulative time).
  • Option A20: Voltage ride through; Suspend regulation drop out time.
  • Option A20: Q(U): Autonomous adjusted VRef is now reset when the DG becomes parallel, when autonomous adjust is enabled, when Q(U) is enabled and when regulation mode is changed over to Q(U).

Changes:

  • Droop curve 1 now uses a more accurate busbar frequency measurement when configured for P(f) operation.
  • Option A20: Fixed cosphi setpoint resolution increased with a factor of 10. Backwards compatibility is not maintained.
  • Option A20: Q(U) open loop time response parameter can now be edited in 10th of a second.

Corrections:

  • No ASC-4 PV irradiance sensor, could make AGC DG's provide inadequate power for mains power export.
  • Cosphi superior setpoints now work with only PV or Battery units on the busbar together with a AGC mains.
  • Volt var handling relative to Vref changed according to tech spec, esp. Autonomous Adj. Vref.
  • Time constant for Vref incorrectly interpreted as open loop time response.
  • When setting parameter #1204 Freq trip type to 'L1 and L2 and L3', the busbar frequency alarms would end up using the generator measurement.
  • Increased measurement inaccuracy at changing frequency could be seen infrequently.

6.04.3

16.11.2021

PM compatibility: 1.24.1

Corrections:

  • Simulating grid frequency via multi-input for droop curve 1 was off by a factor of 10.
  • A change to a different configuration than application 1 using the USW would not persist past a powercycle of the controller.

6.04.2

10.11.2021

PM compatibility: 1.24.1

Corrections:

  • Minimum load was not respected when using droop curve 1.

6.04.1

22.10.2021

Not UL approved version

PM compatibility: 1.24.1

Corrections:

  • Island ramping when loadsharing over CAN or analogue line now works again.
  • Fixed an issue with the EEPROM storage layout.
  • Changing application configuration with jump menu #9160 would not be stored in longterm storage.
  • If the ground relay was enabled and the application configuration was a non PMS single DG, the GB would not open when deloaded.

6.04.0

07.10.2021

Not UL approved version

PM compatibility: 1.24.1

New features:

  • New EIC measurement area included with data validation.
  • Support new J1939 priority for exhaust temperatures (CAT).
  • Extended #1230 G f> 3 and #1260 G f< 3 timers to 2000.0 [s].
  • Power ramps improved. 6- Feedforward control to suppress frequency and voltage disturbances in fixed power, reactive power control (in LFSM situations).

Changes:

  • S nominal import/export set points are obsolete. Both are replaced by one S nominal per measurement area.
  • Maximum timer extended to 3200.0 s on a number of protections (AC, digital inputs, MPU, EIC).

Corrections:

  • Translation now works even though no DU-2 is mounted AND only new language is written.
  • Deload TB before GB opens function works correctly in PEAK SHAVING.
  • PMS priority change via M-Logic or Modbus now works correctly.
  • df/dt now operates on the mains side measurements.

6.03.1

13.09.2021

Not UL approved version

PM compatibility: 1.24.1


Corrections:

  • Freeze regulation during FRT now working correctly.

6.03.0

15.07.2021

Not UL approved version

PM compatibility: 1.24.1

New features:

  • Two new General Purpose PID´s (GP-PID) 5 and 6 are added. Also added new parameters for all GPIDs (1 to 6) to configure the regulator set point.
  • Support of 3 x 2 A/Os on IOM 220/IOM 230 for GP-PID 1 to 6 is added.
  • Support for John Deere Stage V EIC protocol is added.

Changes:

  • TCP/IP security update.

Corrections:

  • Limit events are added in M-Logic for Extended M-Logic Alarms.
  • "Fuel optimization" and "Fuel optimization + running hours" is now working when using percent values.
  • TDU is now able to change to BLOCK mode (requires TDU version 1.3.7.0).
  • Short circuit supervision (option T1) now includes PV and battery units connected (requires ASC-4 version 4.17.0).
  • EIC transmission rate stability is improved.
  • Default IP address is changed from 192.168.2.2 to 192.168.2.21 to match the TDU default address.

6.02.1

06.05.2021

UL approved version

PM compatibility: 1.23.0

Corrections:

  • Plant management Group Tie redundancy is improved in AUTO and ISLAND plants to secure groups without a start signal to start and stop properly when in need of a redundant unit.
  • Corrected the text for IP, subnet, gateway.
  • Corrected that alarm and battery logs where not shown correctly when the number of entries reached maximum.

6.02.0

06.04.2021

Not UL approved version

PM compatibility: 1.23.0

New features:

  • Support for FPT + Iveco Stage V EIC protocol is added.
  • Four new M-Logic alarms with extended delay are added in menu 3620-3650.
  • VDE 4110 support with MAINS unit in power management is added.
  • Event log entry is added when application setup changes.
  • Support of DVC 550 PSS is added.
  • New GOV and AVR step test are added in parameter group #2970.

Changes:

  • CIO alarms are added to Modbus.
  • Minimum set-point is lowered to 10% for low AC voltage alarms.

Corrections:

  • QSK60G EIC auto view is showing correct values.
  • DVC 550/D550 communication when EIC and Ext. Modules DEIF protocols were selected on two CAN ports is corrected.

6.01.2

15.03.2021

Not UL approved version

PM compatibility: 1.22.0

Corrections:

  • The 4-20 mA output of the option EF5 analogue card now works again.
  • Power factor set point on Modbus is now correctly initialized after a power-up.

6.01.1

12.02.2021

Not UL approved version

PM compatibility: 1.22.0

Corrections:

  • Corrected an issue that caused a mains controller to not be able control the PF setpoint (superior cos phi) on genset controllers.
  • N+X now works when Fuel optimisation is in use.
  • Priority update now works when more than 16 gensets or more than 16 mains are present in a plant configuration.
  • PMS priority data is correct maintained internally in all genset controllers.
  • Breaker feedbacks are properly updated on the I/O status and the I/O setup page.

6.01.0

11.01.2021

UL approved version

PM compatibility: 1.22.0

New features:

  •    Added support for Yuchai Diesel+Gas J1939 protocols.
  •    Addded support for Weichai Diesel+Gas J1939 protocols.
  •    Added support for MAN J1939 protocol.

6-00-0

07.01.2021

Not UL approved version

PM compatibility: 1.22.0

   - Initial release.

Auf dieser Seite können Sie Software-Updates für Ihr(e) Produkt(e) herunterladen und sich verschiedene Utility-Tools und Add-ons beschaffen, die Ihnen beim Einrichten und Konfigurieren Ihres Produkts/Ihrer Produkte sowie bei der entsprechenden Fehlersuche behilflich sein können.

Beachten Sie bitte, dass nicht alle unsere Produkte vom Benutzer aktualisiert werden können. Es werden auch nicht alle unsere Produkte mit einem Utility-Tool geliefert. Somit kann die Liste auf dieser Seite nicht als Übersicht unseres kompletten Produktsortiments angesehen werden.

DEIF registriert Ihren Download zusammen mit der verwendeten E-Mail-Adresse, um Ihnen auf Anfrage Informationen zu künftigen Updates zuzusenden.

DEIF kann nicht für die Folgen fehlgeschlagener Produkt-Updates oder die Nutzung von Utility-Tools haftbar gemacht werden. Auch haftet DEIF A/S nicht für die Folgen einer Verhaltensänderung von Produkten aufgrund eines Software-Upgrades. Es obliegt stets dem Anwender, vor der Inbetriebnahme die korrekte Einrichtung und Konfiguration sicherzustellen. Sehen Sie sich vor der Aktualisierung des Produkts das Versionsprotokoll der Software an.

Lizenzvereinbarung für den Software-Download von www.deif.com

Heruntergeladene Software bleibt Eigentum von DEIF. Die Software wurde möglicherweise nicht für gewerbliche Zwecke ausgegeben, sie wurde vollständig oder partiell geändert oder wiederverwendet oder sie wurde an jedwede Drittanbieter verkauft.Auf dieser Seite können Sie Software-Updates für Ihr(e) Produkt(e) herunterladen und sich verschiedene Utility-Tools und Add-ons beschaffen, die Ihnen beim Einrichten und Konfigurieren Ihres Produkts/Ihrer Produkte sowie bei der entsprechenden Fehlersuche behilflich sein können. 

Die aktuellste Version für volle Funktionalität

Wir empfehlen Ihnen, die von uns bereitgestellten Updates zu installieren, um so das volle Potenzial Ihres DEIF-Produkts nutzen zu können.

Die gesamte optimierte Software kann nach Belieben unter www.deif.com heruntergeladen werden. Navigieren Sie dazu zu „Software“ und dann zu „Software-Download“.

Bei Fragen oder Problemen beim Auffinden der entsprechenden Software für Ihr Produkt wenden Sie sich telefonisch unter der Rufnummer +45 96149614 an DEIF A/S oder an die jeweilige lokale DEIF-Niederlassung. Alternativ können Sie uns auch eine E-Mail an support@deif.com senden. Wir helfen Ihnen gerne weiter.

Press release, June 2015

Information on product improvement specifically related to “older” DEIF A/S ML-2 products.