Multi-line 300 PPU 300 ver. 1.x.x.

Diese Software passt zu den folgenden DEIF-Produkten:

Sie starten das Herunterladen von 1.0.4.1

Die wichtigsten Änderungen seit der letzten Version:

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.10.0

PPU 300

Corrections:

  • BSP version 3.0.1.0 supported.
  • Negative fixed power deload dit not work. Instead of ramping to zero, it increases load.
  • AVR/GOV output selection failure alarm triggered after software upgrade.

DU 300

New features:

  • Support for multiple menu levels.
  • Display shows a pop-up window for the user before going into service mode.
  • Informs the user about development of the software.

Changes:

  • Support for PlantSupervision ver 1.0.5.0.

Corrections:

  • IOM3.4: DO's are not shown on display and in PICUS.
  • Display is not loading min. and max. from parameters when they are changed.
  • Power derate temperature is not shown on DU until power cycle.
  • When changing type, DU sometimes freezes until it restarts.
  • DU300 reboot in view designer.
  • Not able to close alarm pop-up.
  • Alarm "trigger value" is not updated if the alarm is already in the alarm list.
  • DU300 does not check versions for individual REST resources.
  • View designer cannot add counters to counters template.
 

Ver. Datum Beschreibung

1.0.4.1

04.03.2019

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.10.0

PPU 300

Corrections:

  • BSP version 3.0.1.0 supported.
  • Negative fixed power deload dit not work. Instead of ramping to zero, it increases load.
  • AVR/GOV output selection failure alarm triggered after software upgrade.

DU 300

New features:

  • Support for multiple menu levels.
  • Display shows a pop-up window for the user before going into service mode.
  • Informs the user about development of the software.

Changes:

  • Support for PlantSupervision ver 1.0.5.0.

Corrections:

  • IOM3.4: DO's are not shown on display and in PICUS.
  • Display is not loading min. and max. from parameters when they are changed.
  • Power derate temperature is not shown on DU until power cycle.
  • When changing type, DU sometimes freezes until it restarts.
  • DU300 reboot in view designer.
  • Not able to close alarm pop-up.
  • Alarm "trigger value" is not updated if the alarm is already in the alarm list.
  • DU300 does not check versions for individual REST resources.
  • View designer cannot add counters to counters template.
 

1.0.4.1

19.11.2018

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.8.0

PPU 300

Corrections:

  • BSP version 3.0.1.0 supported.
  • Negative fixed power deload dit not work. Instead of ramping to zero, it increases load.
  • AVR/GOV output selection failure alarm triggered after software upgrade.

DU 300

  • No changes

 

 

1.0.4.0

06.07.2018

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.8.0

PPU 300

New features:

  • Now possible to use 16 controllers in single line

DU 300

  • No changes

 

1.0.3.0

20.04.2018

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.8.0

PPU 300 

New features:

  • CODESYS add-on
  • Frequency-dependent droop regulation
  • Support of GAM3.2 module with stand-alone possible
  • Able to abort "Lamp test" dialogue box
  • Power ramp configuration improved for better user experience
  • Selectable offsets for fixed P, Q and CosPhi regulation
  • Alarms made available in custom logic
  • Analogue I/O made available in custom logic
  • Parameter values made available in custom logic
  • Use external analogue signal as regulator set point
  • Alarm for F/V not OK made independent of GOV/AVR configuration
  • Power regulator set point range extended to -100 % to +100 %
  • GOV/AVR status display on PICUS and display
  • Regulation on SG 
  • Freeze regulation
  • Support of IOM3.4
  • Analogue value compare and operate function in custom logic

Changes: 

  • Optimised menu layout for better user experience
  • Improved ACM firmware update sequence

Corrections:

  • Compact breaker, optimised spring load sequence
  • "Blackout detection mismatch" functionality corrected
  • Fixed missing trip alarms
  • Manual regulation not possible with certain regulator settings
  • Fixed that "GB open-and-stop command" was ignored
  • Fixed that running detection by means of digital input could be delayed (affecting "Engine ready LED")
  • Fixed that in manual regulation mode, relay output could sometimes be left in "activated" state
  • Fixed that "Remove start" input could cause unintended short activation of crank relay
  • Fixed that cancelling a stop sequence could result in engine stopping anyway
  • Fixed that command "Open generator breaker and stop engine" could leave engine running
  • Fixed that running detection would not terminate crank timer
  • Fixed that alarms "GOV and AVR regulation error" would not be triggered
  • Alarms are always shown, even if configured as "suppressed"
  • Active start block alarm can no longer abort cooldown sequence
  • Genset temperature power derate functionality improved
  • "Start engine and close GB" command is now blocked by "Block engine start" command
  • Alarm on controller with breaker feedback error could result in breaker opening and engine stopping
  • DG suddenly becoming last controller on busbar during de-load, would trip its breaker
  • Detection of "Vector mismatch" improved
  • Fixed that "Freeze regulation" could leave relay output in "activated" state
  • Fixed that "BTB trip" command did not cancel synchronisation
  • Engine state in switchboard will now resolve to "Ready" instead of "Not Ready"

DU 300

New features:

  • Livedata configurator (View design)
  • Regulator screen (GOV/AVR)
  • Livedata dynamic reload integration
  • Message box popup

Changes:

  • Added display specific support for introspecting memory data
  • Update ID and labels on pair screen when entering the screen
  • Custom curves max precision changed from 2 to 8
  • Support for REST 1.0.4.0
  • Improvement to log output
  • Added direction to command list

Corrections:

  • DU relay not working
  • ML300 Backwards compatibility issues of DU
  • Parameter graph, special case fail
  • Livedata scales are not appearing
  • Event log was not telling which "command" (button) was pressed.
  • Blocking pop-up on DU 300 if controller software does not match.
  • Counter pop-ups now working correctly.
  • Display alarm list deadlock removed.
  • DU 300 able to change from service mode to app mode.
  • Inhibit counter on the parameters was showing wrong number of inhibits
  • Comma insted of dot between the (rack#,slot#) presentation of card name
  • Identify did not work when logged on
  • Corrections to dynamic reload of livedata
  • Corrections to eventlog navigation
  • Update value list on changes
  • Applying broadcast storm filter on startup
  • Display not showing Priority
  • Pair controller not working correctly with rework.

 

1.0.2.0

29.09.2017

New features:

  • Acces to all alarm status information from CODESYS
  • Extended status information for alarm functionblocks in CODESYS   

Changes: 

  • Software mismatch on hardware module(s) alarm only occur if first, second or third digit on IO card version is changed
  • New EIM 3.1 software 2.0.1.0

1.0.1.0

25.08.2017

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.6.0

PPU 300 

New features:
   1  - 4 directional over-current alarms have been added to BTB (ANSI 67).
   2  - 2 directional over-current alarms have been added to SC and SG (ANSI 67).
   3  - Support of lamp test function.
   4  - Support of controller identify function.
   5  - Active regulator mode will be deactivated if a new is requested.
   6  - Additional information regarding alarms, breaker-, busbar- and generator status made available on Modbus.
   7  - Added "Critical process error"" alarm.
   8  - Last DG will trip if no other feeders are closed in the plant.

Changes:
   1  - "Power supply" parameter menu renamed to "Hardware".
   2  - "Network" parameter group moved to "Hardware" instead of "Utility". 
   3  - "Reset ratio" renamed to "Hysteresis" for protection alarms.
   4  - General check that "Nominal settings" cannot be configured to 0.
   5  - "Fixed power factor" renamed to "Fixed CosPhi".
   6  - "Analog" renamed to "Analogue".
   7  - "System not OK" alarm action is changed to "Warning".
   8  - New ACM 3.1 software 4.0.1.4.
   9  - New PCM 3.1 software 2.0.0.2.
   10 - The others are version 1.0.3.0.
   11 - "Directional over-current" alarm min. and max. set points have been extended to -300 % and 300 %.
   12 - Only one regulator request is accepted if more have been received.
   13 - It is possible to configure action on "System not OK" alarm.

Corrections:
   1 - Controller types SC, SG and BTB stop synchronising if measure feedback disappears.
   2 – Regulator could freeze if regulators were used in custom logic.
   3 - Regulator continued to regulate after feedback failure on GB.


DU 300

New features:
- Implemented first part of custom stylesheets
- Curves have been added to parameters
- Lamp test
- Identify feature to communication screen
- Units change on display
                      
Changes:
- Navigation and editing in I/O input text is now possible from the keyboard
- Default live data views updated
- Edit line design has been updated
- Updated counter screen to use states
- Default text in keyboard will show resolution
- Live data screens dynamic update (step 1)
- REST version control improvement step 1 (A+B match)
- REST version control improvement step 2 (new REST resource implementation)
- Live data dial meter and vertical bar widgets improved
- Production screen changed to versions screen, production data now visible in about screen
- Added DNS possibility to communication screen
- Added IPv6 address to communication screen
- Live data using REST to build screen and widgets
- Terminal values updated to only show allowed precision
- Updated help screens
                      
Corrections:
- Custom inhibit does no longer clear other inhibit flags
- Placeholder text from previous screen does no longer influence logon screen
- Handling of empty list in pair screen
- Pair screen automatically keeps rescanning for controllers if previously connected to a controller
- Elements in parameters are represented in the same order as in the base unit
- Preparation of lists in the application improved
- Removed dot key from keyboard when value is integer, or precision is zero
- Network off pop-up did not show the first time the display lost connection
- Do not allow user to press OK in empty pair list
- Cardlist serial to be a string instead of integer
- Display reboots after setting up AVR
- No longer showing all functions when function groups is empty
- Cleaned up warnings
- Not able to enable/disable the alarm "Ethernet redundancy broken"
 

1.0.0.3

12.04.2017

This software package consist of:

  • Multi-line 300, PPU 300
  • Bundled with DU 300 SW version 1.0.5.0

 

PPU 300

Corrections:
   1- Trip and stop action did not stop the engine in switchboard mode 
   2- Customlogic inputs was evaluated wrong in scan
   3- Sync. type was changed back from Static to dynamic after a power cycle

 

DU 300

No changes

1.0.0.2

14.03.2017

Corrections:

  • Start and close command now works correctly if “Voltage and frequency OK” timer has been increased.
  • Open and stop command can also stop the engine if breaker is opened, when command has been sent.

 


1.0.0.0

21.12.2016

PPU 300: Initial release

DU 300 ver. 1.0.5.0:

New features:

  • Added placeholder text when the label is completly empty, when you enter an I/O name, the current name of the IO will be shown.
  • Support of 4 line pop-up in the display.
  • Displays the variant on the info/about screen.
  • New pair feature (select base unit).

Changes:

  • DU registration of 4 new languages.
  • DU REST 1.0.2.0 support.
  • Update DU help files.
  • Added REST version to "About screen" in row 3.
  • Made it possible to take pictures of the first pair screen

Corrections:

  • Changed home screen Alarm 8000002 to Alarms 800025 to match the path.
  • Removed two arrows that were shown in parameter groups that was not supposed to be there.
  • Display could have problems, connecting to base units if it was connected in a daisy chain.
  • Making the algorithm responsible for showing/hiding pop-up windows.
  • Updating status text, and diodes in DU is made faster.
  • Crash in start-up sequence removed.
  • Corrected some filtering of allowed functions.
  • Remove illegal references to parameters.
  • Incorrect text shown when valueList had less than 2 elements removed.
  • If alarm screen is detected in the screen history, the current screen is rewound to that alarm screen.
  • DU updating speed improved.
  • Pop-up header characters clip adjusted.
  • IO scale: impossible to select a custom scale with only 1 point.
  • Header text initialised.
  • Pairing pop-up cuts of text on very long labels.
  • Controller for selecting base unit.
  • Appending empty unit to analogue output functions not possible.
  • DU start-up screen has been corrected.
  • Label corrected to "Restart" display instead of "Reset".

Auf dieser Seite können Sie Software-Updates für Ihr(e) Produkt(e) herunterladen und sich verschiedene Utility-Tools und Add-ons beschaffen, die Ihnen beim Einrichten und Konfigurieren Ihres Produkts/Ihrer Produkte sowie bei der entsprechenden Fehlersuche behilflich sein können.

Beachten Sie bitte, dass nicht alle unsere Produkte vom Benutzer aktualisiert werden können. Es werden auch nicht alle unsere Produkte mit einem Utility-Tool geliefert. Somit kann die Liste auf dieser Seite nicht als Übersicht unseres kompletten Produktsortiments angesehen werden.

DEIF registriert Ihren Download zusammen mit der verwendeten E-Mail-Adresse, um Ihnen auf Anfrage Informationen zu künftigen Updates zuzusenden.

DEIF kann nicht für die Folgen fehlgeschlagener Produkt-Updates oder die Nutzung von Utility-Tools haftbar gemacht werden. Auch haftet DEIF A/S nicht für die Folgen einer Verhaltensänderung von Produkten aufgrund eines Software-Upgrades. Es obliegt stets dem Anwender, vor der Inbetriebnahme die korrekte Einrichtung und Konfiguration sicherzustellen. Sehen Sie sich vor der Aktualisierung des Produkts das Versionsprotokoll der Software an.

Lizenzvereinbarung für den Software-Download von www.deif.com

Heruntergeladene Software bleibt Eigentum von DEIF. Die Software wurde möglicherweise nicht für gewerbliche Zwecke ausgegeben, sie wurde vollständig oder partiell geändert oder wiederverwendet oder sie wurde an jedwede Drittanbieter verkauft.Auf dieser Seite können Sie Software-Updates für Ihr(e) Produkt(e) herunterladen und sich verschiedene Utility-Tools und Add-ons beschaffen, die Ihnen beim Einrichten und Konfigurieren Ihres Produkts/Ihrer Produkte sowie bei der entsprechenden Fehlersuche behilflich sein können. 

Die aktuellste Version für volle Funktionalität

Wir empfehlen Ihnen, die von uns bereitgestellten Updates zu installieren, um so das volle Potenzial Ihres DEIF-Produkts nutzen zu können.

Die gesamte optimierte Software kann nach Belieben unter www.deif.com heruntergeladen werden. Navigieren Sie dazu zu „Software“ und dann zu „Software-Download“.

Bei Fragen oder Problemen beim Auffinden der entsprechenden Software für Ihr Produkt wenden Sie sich telefonisch unter der Rufnummer +45 96149614 an DEIF A/S oder an die jeweilige lokale DEIF-Niederlassung. Alternativ können Sie uns auch eine E-Mail an support@deif.com senden. Wir helfen Ihnen gerne weiter.

Press release, June 2015

Information on product improvement specifically related to “older” DEIF A/S ML-2 products.