Select your business area

We use this information to provide content associated with segment of your choice.
You can change your selection any time.

Multi-line 2 AGC 150 Application Software

Diese Software passt zu den folgenden DEIF-Produkten:

Sie starten das Herunterladen von 1.04.2

Die wichtigsten Änderungen seit der letzten Version:

PM compatibility: 1.17.2.

Corrections:

  •    TEST type in StandAlone (option S1) is limited to SIMPLE TEST.
  •    Limit evaluation of multi-input 23 alarm for use in M-Logic is now working.
  •    Included CAN Start/Stop in the Hatz proprietary CM1 telegram.
  •    Current handling of TIER 4 icons for the Hatz protocol.
  •    Read Aftertreatment 1 Intake Gas telegram for the Hatz protocol.
  •    Necessary to force a regeneration until current feedback is received from ECU.
  •    Fuel optimization + running hours does not swap DG's at fixed load.

Ver. Datum Beschreibung

1.04.2

22.09.2020

PM compatibility: 1.17.2.

Corrections:

  •    TEST type in StandAlone (option S1) is limited to SIMPLE TEST.
  •    Limit evaluation of multi-input 23 alarm for use in M-Logic is now working.
  •    Included CAN Start/Stop in the Hatz proprietary CM1 telegram.
  •    Current handling of TIER 4 icons for the Hatz protocol.
  •    Read Aftertreatment 1 Intake Gas telegram for the Hatz protocol.
  •    Necessary to force a regeneration until current feedback is received from ECU.
  •    Fuel optimization + running hours does not swap DG's at fixed load.

1.04.1

29.07.2020

Version 1.04.1 based on 1.04.0

PM compatibility: 1.17.2

Corrections:

  • Errors regarding powermanagement applications with PV, ASC and battery controller corrected.
 

1.04.0

29.06.2020

Version 1.04.0 based on 1.03.1

PM compatibility: 1.17.2

New features:

  • Controller type 'Hybrid DG unit' added with support of PV inverter and weather protocols.
             • Minimum genset load in island
             • Modbus master support
             • Communication RS485 menu/setup updated with Modbus Master
             • Load calculation in terms of solar power
             • POA and BOM for calculating P max
             • PV energy counters
             • PV breaker feedback
             • Monitoring of inverter
             • Inverter start/stop logic
             • Start/Stop logic for DG in MPE with PV 
             • PV semi start/stop from display

  • Support of the new input configuration interface introduced.
  • Added support for MAN engine protocol.
  • Added support for Hatz engine protocol.
  • Added support for Yuchai engine protocol.
  • Added support for Weichai engine protocol.

Corrections:

  • Unwanted appeareance of 30min data storage alarm on MAINS eliminated.
  • Error regarding CIO module communication after communication errors corrected.
 

1.03.1

14.05.2020

PM compatibility: 1.17.2.

Corrections:

  • Analog output limits for the transducer output are corrected.
  • Transducer input range is extended on multi inputs to support the setup of limits corrected in #1.
  • STOP button has always a lid on the genset when running German rule, V0108.

1.03.0

03.04.2020

PM compatibility: 1.17.2

New features:

  •    DVC 550 and D550 are now supported by the AGC.
  •    Configurable amount of units for triggering Fatal CAN Error alarm, added in menu 8800.

Changes:

  •    Emulated value for I>> alarms added.
  •    Easy Connect is no longer blocking DG start in single DG applications.

Corrections:

  •    In AMF situations where the mains had no TB, and #7065 mains fail ctrl was set to "Start engine" and the DGs had to connect through a BTB to supply the mains, the MB would not open as it did not have information about whether or not the DGs Hz/V OK timer had run out. And as the MB would not open the BTB would not close resulting in a deadlock. This has been corrected.
  •    TB power capacity overrule timer will now run if there is an active MB trip failclass or the MB cannot be closed.
  •    Ring bus applications: If BTBs were closed at and under application configuration, opening a BTB could cause a DG to start without a proper start signal.
  •    Fixed a situation where opening a semi BTB, in a plant with an active start signal, would cause a DG to briefly engange its start prepare relay.
  •    In a plant where all DGs are divided by open BTBs, if for example, DG1 is running and needs help from DG2, DG2 would start and close its breaker, then synchronize the BTB, and as the BTB would close, DG3 would briefly engange its start prepare relay. This has been fixed.
  •    PMS + ISLAND + SEMI + GUIDED MIMIC: Start/stop buttons LED visible when relevant on genset.

1.02.0

26.03.2020

PM compatibility: 1.17.0.

New features:

  •    Two new EIC aftertreatment alarms have been added: "High SOOT warning" and "High SOOT shutdown".

Changes:

  •    Vector jump, df/dt, positive busbar sequence and directional over-current are now available in CORE MAINS and CORE BTB.
  •    New TIER 4 icons for JCB EIC are added.

Corrections:

  •    Parameter handling could in special cases cause decimals to be handled incorrectly in the display menu. This is corrected.
  •    Problems with freeze and white screen are now prevented.
  •    Analogue values from CIO 308 are now shown correctly in view-lines.
  •    JUMP menu causing unwanted parameter change is corrected.
  •    JUMP menu freeze is now prevented.
  •    Overspeed 2 menu (4520) is now shown correctly.
  •    GUIDED mimic is corrected with external breaker, so GB ON/OFF buttons do not lit up.

1.01.0

19.12.2019

PM compatibility: 1.17.0.

New features:

  • EIC: JCB J1939 protocol is added.
  • EIC: DEF level shown on lower tiny line in measure views. 
  • Stand Alone (option S1) is implemented. Breaker selection is extended with 'No breaker' and 'External breaker'.
  • LED colors can now be changed. An option to select a different LED color behavior in parameter 6084.
  • Now it is possible to change the source address for PGN GC1 and CM1 independently of each other for all engine protocols.

Corrections:

  • BTB can now be part of a plant with CORE units.

1.00.3

22.10.2019

PM compatibility: 1.17.0

Corrections:

  • External BTB position feedbacks are now working again.
  • Phase sequence error alarms are now working 3W3 coupling.
  • Service timers can now be reset.
  • Translated texts for I/O texts in Service View are now shown correctly.

1.00.2

05.08.2019

Version 1.00.2 based on 1.00.1

PM compatibility: 1.17.0

Corrections:

  •    Deloading the TB is now properly handled in test mode when parameter #8273 "Deload TB back sync." is enabled
  •    Multi inputs could go into overflow when set to voltage type
  •    Internal analog outputs (52/55) now works correct when used with GP PID.
  •    Genset priority would update even though the user had not issued an update.
  •    If mains ATS is active, and TB is closed onto a healthy busbar, and the controller is powercycled, the TB no longer opens and closes on power up.
  •    When sending a stop command during idle start the idle relay is kept closed.
  •    Fixed situations where multi start would not work correctly in ISLAND and AMF applications.
  •    M-Logic flag "Run all available island DG's" starts all DG's when activated.
  •    Mimic for BTB and MAINS with External breaker updated, so the respective buttons (open/close) are not visible.
  •    Various parameters added to parameter tree
  •    Improved Easy Connect functionality:
          - Rapid menu changes prevented
          - Info text on removed units
          - Possibility to remove the other unit with pop-up when only 2 in plant
          - Better handling of fault situations (Appl. hazard or Duplicate CAN ID)
          - Removed units are no longer blocked from running
          - Faster indication of changes on the other units

1.00.0

30.04.2019

PM compatibility: 1.17.0

  • Initial release

Auf dieser Seite können Sie Software-Updates für Ihr(e) Produkt(e) herunterladen und sich verschiedene Utility-Tools und Add-ons beschaffen, die Ihnen beim Einrichten und Konfigurieren Ihres Produkts/Ihrer Produkte sowie bei der entsprechenden Fehlersuche behilflich sein können.

Beachten Sie bitte, dass nicht alle unsere Produkte vom Benutzer aktualisiert werden können. Es werden auch nicht alle unsere Produkte mit einem Utility-Tool geliefert. Somit kann die Liste auf dieser Seite nicht als Übersicht unseres kompletten Produktsortiments angesehen werden.

DEIF registriert Ihren Download zusammen mit der verwendeten E-Mail-Adresse, um Ihnen auf Anfrage Informationen zu künftigen Updates zuzusenden.

DEIF kann nicht für die Folgen fehlgeschlagener Produkt-Updates oder die Nutzung von Utility-Tools haftbar gemacht werden. Auch haftet DEIF A/S nicht für die Folgen einer Verhaltensänderung von Produkten aufgrund eines Software-Upgrades. Es obliegt stets dem Anwender, vor der Inbetriebnahme die korrekte Einrichtung und Konfiguration sicherzustellen. Sehen Sie sich vor der Aktualisierung des Produkts das Versionsprotokoll der Software an.

Lizenzvereinbarung für den Software-Download von www.deif.com

Heruntergeladene Software bleibt Eigentum von DEIF. Die Software wurde möglicherweise nicht für gewerbliche Zwecke ausgegeben, sie wurde vollständig oder partiell geändert oder wiederverwendet oder sie wurde an jedwede Drittanbieter verkauft.Auf dieser Seite können Sie Software-Updates für Ihr(e) Produkt(e) herunterladen und sich verschiedene Utility-Tools und Add-ons beschaffen, die Ihnen beim Einrichten und Konfigurieren Ihres Produkts/Ihrer Produkte sowie bei der entsprechenden Fehlersuche behilflich sein können. 

Die aktuellste Version für volle Funktionalität

Wir empfehlen Ihnen, die von uns bereitgestellten Updates zu installieren, um so das volle Potenzial Ihres DEIF-Produkts nutzen zu können.

Die gesamte optimierte Software kann nach Belieben unter www.deif.com heruntergeladen werden. Navigieren Sie dazu zu „Software“ und dann zu „Software-Download“.

Bei Fragen oder Problemen beim Auffinden der entsprechenden Software für Ihr Produkt wenden Sie sich telefonisch unter der Rufnummer +45 96149614 an DEIF A/S oder an die jeweilige lokale DEIF-Niederlassung. Alternativ können Sie uns auch eine E-Mail an support@deif.com senden. Wir helfen Ihnen gerne weiter.

Press release, June 2015

Information on product improvement specifically related to “older” DEIF A/S ML-2 products.